Configuring UniFi Access Control Hub Terminals
This article explains how to configure terminal settings in the Access application after wiring devices (e.g., locks, door position sensors, push-to-exit buttons, and motion sensors) to your UniFi Access Control Hubs for optimal performance and customization. If you're looking to understand the hub's input/output terminals, click here. For hub comparisons, click here.
| Update your UniFi OS, Access application, and Access devices to the latest versions for the newest features and optimal performance. |
Configuring Output Terminal Settings
Output terminal settings such as locks, door operators, sirens, and chimes are configured in Access application > Devices > select a hub > Settings > Terminal > Terminal Manager.
Door Lock Settings
After a door lock is wired to the hub, set the duration for which a door remains unlocked after access is granted.
- Door Hub, Door Hub Mini, Access Ultra: Navigate to Lock > Trigger Duration.
- Enterprise Access Hub, Retrofit Hub: Navigate to Location > Lock > Trigger Duration.
- Gate Hub: Navigate to Side Door Lock > Trigger Duration.
- Elevator Hub: Navigate to Floor Terminals > Trigger Duration. Then set the Terminal Mode to Fail-Safe or Fail-Secure. Learn more
Door Operator Settings
After a door operator is wired to the hub for automated door opening and closing, set a delayed door opening and unlock duration for safety and accessibility needs.
- Door Hub: Navigate to Auxiliary (AUX) > Mode > Door Opener > Delay Door Opening.
-
Enterprise Access Hub, Retrofit Hub: Navigate to Location > AUX > Mode > Door Opener > Delay Door Opening.
- Open Door After: Set when the operator activates after a user is authenticated and unlocks the door.
- Trigger Duration: Set how long the door remains open.
Siren Settings
After a siren is wired to the hub, set the duration for which the door can remain open past its unlock duration before the siren sounds.
- Door Hub: Navigate to Auxiliary (AUX) > Mode > Siren > Trigger Open Door Alarm.
- Enterprise Access Hub, Retrofit Hub: Navigate to Location > AUX > Mode > Siren > Trigger Open Door Alarm.
- Gate Hub: Navigate to AUX > Siren and select gate, side door, or both.
Chime Settings
After a chime is wired to the hub, set the ring duration when triggered by a doorbell press.
- Door Hub: Navigate to Auxiliary (AUX) > Mode > Chime > Ring Duration.
- Enterprise Access Hub, Retrofit Hub: Navigate to Location > AUX > Mode > Chime > Ring Duration.
If you're using a UniFi Chime, click here.
Configuring Input Terminal Settings
Input terminal settings such as motion sensors, request-to-exit, doorbell buttons, and door position sensors are configured in Access application > Devices > select a hub > Settings > Terminal > Terminal Manager.
Request-to-Exit Device Settings
After a request-to-exit (REX) device is wired to the hub for free egress, set the trigger level to close active (NO) or open active (NC) based on the device's specifications.
-
Door Hub:
- For motion sensor: Navigate to Motion.
- For push-to-exit button or panic bar: Navigate to Button > Mode > Unlock Door.
- Door Hub Mini, Access Ultra: Navigate to Exit Request.
- Enterprise Access Hub, Retrofit Hub: Navigate to Location > Exit Request > Mode > Unlock Door.
- Gate Hub: Navigate to Side Door > Exit Request.
Doorbell Button Settings
After a doorbell button and third-party chime are wired to the hub for entry requests, set the trigger level to close active (NO) for most scenarios. However, settings may vary by manufacturer.
- Door Hub: Navigate to Button > Mode > Ring/Trigger Chime.
- Enterprise Access Hub, Retrofit Hub: Navigate to Location > Exit Request > Mode > Ring/Trigger Chime.
If you are using UniFi Chimes, click Select UniFi Chimes to specify the chimes to ring when the doorbell button is pressed.
Door Position Sensor Settings
After a door position sensor (DPS) is wired to the hub for door status monitoring, set the trigger level to open active (NC) for most scenarios. However, settings may vary by manufacturer.
- Door Hub, Door Hub Mini: Navigate to Door Position.
- Enterprise Access Hub, Retrofit Hub: Navigate to Location> Door Position.
- Gate Hub: Navigate to Gate > Gate Position or Side Door > Side Door Position.
Emergency Settings
After a fire panel is wired to the hub for fire detection, configure automatic emergency mode activation in the event of an emergency.
- Navigate to Emergency > Emergency Mode and select Lockdown or Evacuation.
- (Optional) Tick the Activate This Mode for All Locations at This Site checkbox to enable emergency mode across all hubs at the same site.
- Set the Trigger Level to Close Active (NO) or Open Active (NC).
| Important: Emergency mode triggered by the fire panel cannot be deactivated via the Access application, Access mobile app, or Admin Mode on a reader. However, if Activate This Mode for All Locations at This Site is enabled, you can still deactivate the mode for individual doors that are not triggered by the fire panel at Dashboard > select a door > Overview > Deactivate. |